ABB i-bus KNX SUG/U 1.1 Product Manual page 23

Split unit
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Limit Setpoint temperature range
Options:
Yes: Enables the 1-bit group object Deactivate setpoint temperature limit.
Note
If you activate Setpoint temperature limit while the current setpoint temperature is outside the setpoint
temperature range, the setpoint temperature will be set to the upper or lower limit of the range.
Note
The setpoint temperature limit is activated after the download.
Note
However, activating the priority (Forced operation) takes the setpoint temperature limit into account.
Dependent parameters:
This parameter sets limits for heating and cooling. If a temperature above the Max. heating setpoint
temperature or below the Min. cooling setpoint temperature is sent to the Split Unit Gateway, the
highest/lowest permissible value respectively is sent to the unit. Status values are updated accordingly.
Note
You need to check whether the split unit supports the required temperature range. You can read this
in the ETS app or refer to the manufacturer documentation for the split unit.
No
Yes
Max. heating setpoint temperature
Options:
16...23...32°C
Min. cooling setpoint temperature
Options:
16...18...32°C
SUG/U 1.1 | 2CDC508171D0201 21