ABB i-bus
KNX
Commissioning
No.
4
The fan speed status is always shown by the 1 byte object, even if Control fan speed with object parameter is set to 1 bit
up/down on the Split Unit settings page.
The coding of the status object is dependent on the setting in the Coding of 1 byte parameter.
0%=Auto; 33%=Low, 66%=Medium, 100%=High
4
The fan speed status is always shown by the 1 byte object, even if Control fan speed with object parameter is set to 1 bit
up/down on the Split Unit settings page.
The coding of the status object is dependent on the setting in the Coding of 1 byte parameter.
0=Auto, 1=Low, 2=Med, 3=High
5
When a telegram is received on this object, the fan speed reduces or increases by one speed.
Value 1: Increases fan speed
Value 0: Reduces fan speed
Available fan speeds are: Automatic, Low, Medium, High
If the fan reaches High, a further telegram with the value 1 has no effect.
If the fan is set to Automatic, a further telegram with the value 0 has no effect.
6
This object sets the operating mode for the split unit.
The operating modes set on receipt of a corresponding value are as follows:
0=Auto
1=Heating
3=Cooling
9=Ventilation
14=Drying
All other values are discarded.
38 2CDC508171D0201 | SUG/U 1.1
Function
Status Fan speed
Dependent on parameter
Status Fan speed
Dependent on parameter
Fan up/down
Dependent on parameter
Operation mode
Dependent on parameter
Group object name
Split unit
Enable group object "Status Fan speed" 1 byte
Split unit
Enable group object "Status Fan speed" 1 byte
Split unit
Control fan speed with object
Split unit
Always visible
Data type
Flags
1 byte
C, R, T
DPT 5.001
1 byte
C, R, T
DPT 5.010
1 bit
C, W
DPT 1.007
1 byte
C, W
DPT 20.105