ABB i-bus KNX SUG/U 1.1 Product Manual page 45

Split unit
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
25
This object starts and stops horizontal and/or vertical swing.
1 = vertical swing starts
0 = vertical swing stops
Note
On certain split units, the slats move to a specific position when swing is stopped.
26
This object indicates the status of vertical swing.
1 = vertical swing started
0 = vertical swing stopped
27
This object starts and stops horizontal swing.
1 = starts horizontal swing
0 = stops horizontal swing
Note
On certain split units, the slats move to a specific position when swing is stopped.
Function
Vertical Swing
Dependent on parameter
Status Vertical swing
Dependent on parameters
Horizontal Swing
Dependent on parameter
Group object name
Split unit
Enable "Swing"
See Enable "Swing"
(horizontal and vertical), p. 24
Split unit
Enable "Swing" and
Enable group object "Status Swing" 1 bit
See Enable "Swing"
(horizontal and vertical), p. 24
Split unit
Enable "Swing"
See Enable "Swing"
(horizontal and vertical), p. 24
Data type
Flags
1 bit
C, W
DPT 1.001
1 bit
C, R, T
DPT 1.001
1 bit
C, W
DPT 1.001