Control fan speed with object
Options:
Depending on the option you select, this enables the the by 1 byte Fan speed group object and/or the 1 bit
Fan up/down group object.
The Split Unit Gateway receives the fan speed from a KNX operating device via this object and sends it to
the split unit.
If the split unit supports more than 3 fan speeds, only 3 speeds are mapped to Low/Med/High.
Example
If the split unit supports 5 fan speeds, speed 1 is mapped to Low, speed 3 to Med and speed 5 to High,
in which case speeds 2 and 4 are not used.
22 2CDC508171D0201 | SUG/U 1.1
1 byte
1 bit up/down
1 bit up/down and 1 byte
Dependent parameter:
Coding of 1 byte
Options:
0%=Auto, 1-33%=Low, 34-66%=Med, >66%=High
0=Auto, 1=Low, 2=Med, 3=High