ABB i-bus KNX SUG/U 1.1 Product Manual page 21

Split unit
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Reaction after bus voltage recovery,
download and ETS reset
Options:
Do not repeat last infrared command: The last command sent before bus voltage failure is not resent
to the split unit. If the split unit was operated with a remote control during the bus voltage failure, it is
possible (until the next command via KNX) that the status of the split unit will not match the KNX
status.
Repeat last infrared command: The last command sent before bus voltage failure is resent to the split
unit. This ensures that the split unit is restored to the required state in the event that the unit was
operated with a remote control during bus voltage failure.
User-defined: The reaction can be individually parametrized for each function.
(On/Off, Setpoint temperature, Operation mode, Fan speed, Swing, Silent Mode).
Additional parameters will appear accordingly.
Access with i-bus Tool
Options:
Note
The i-bus Tool
Read and write: The i-bus
can be executed.
Read only request: The i-bus
Disabled: The tool has no access to the device.
Do not repeat last infrared command
Repeat last infrared command
User-defined
Read and write
Read only request
Disabled
®
is an optional diagnosis tool that is available free of charge on our website.
®
Tool has full access to the device and all functions supported by the tool
®
Tool only has read access; no commands can be sent to the device.
SUG/U 1.1 | 2CDC508171D0201 19