ABB i-bus
KNX
Commissioning
No.
12
This object switches the split unit on and off.
1 = split unit switches on
0 = split unit switches off
If a switching off delay is parametrized and activated, the split unit only switches off after the specified delay.
13
This object indicates the status of the On/Off function.
1 = split unit is on
0 = split unit is off
If a switching off delay has been specified, the unit is not switched off until this has elapsed.
14
The On/Off delay function delays switching off the split unit (i.e. sending the infrared command) by the parametrized time.
Receipt of a telegram with the value 1 on the "Deactivate On/Off delay" object deactivates the switching off delay.
Telegram value
15
Activating the Forced operation function (sending a telegram with the value 1 on the object) sets the split unit to its
parametrized state for forced operation.
When the Forced operation function is deactivated (telegram with the value 0 on the object), the lower-priority function
(Window contact) is evaluated, provided it is enabled.
If the Window contact function is not enabled or activated, the last non-priority command received via the KNX bus is
executed.
40 2CDC508171D0201 | SUG/U 1.1
Function
On/Off
Dependent on parameter
Status On/Off
Dependent on parameter
Deactivate On/Off delay
Dependent on parameter
1 = Deactivates switching off delay
0 = Activates switching off delay
Forced operation
Dependent on parameter
Group object name
Split unit
Always visible
Split unit
Enable group object "Status On/Off" 1-bit
Split unit
Enable "On/Off delay" function
Function
Enable "Forced operation" function
Data type
Flags
1 bit
C, W
DPT 1.001
1 bit
C, R, T
DPT 1.001
1 bit
C, W
DPT 1.003
1 bit
C, W
DPT 1.003