Compressor Controller - McQuay WSC Operating Manual

Microtech ?? for centrifugal chillers and templifiers
Hide thumbs Also See for WSC:
Table of Contents

Advertisement

Table 3, Unit Controller, Digital Outputs
#
NO1
NO2
NO3
NO4
NO5
NO6
NO7
NO8
NO9
NO10
Table 4, Unit Controller, Analog Outputs
#
Description
Cooling Tower Bypass Valve Position
Y1
Y2
Cooling Tower VFD Speed
Y3
Electronic Expansion Valve (EEV)

Compressor Controller

The compressor controller's primary function is controlling and protecting the compressor. No
setpoint inputs are made with it. There is one compressor controller for each compressor on a dual
chiller unit. The compressor controller receives, processes, and sends data to other controllers and
devices and to the compressor starter or variable frequency drive (VFD). With some operator
intervention the compressor controller can operate the compressor(s) if the unit controller and/or
the operator interface touch screen are unavailable. Inputs and outputs are as follows:
Table 5, Compressor Controller, Analog Inputs
#
B1
Oil Sump Pressure
Oil Supply Pressure to Compressor
B2
B3
Evaporator Refrigerant Pressure
B4
Oil Sump Temperature
B5
Compressor Suction Temperature
B6
Condenser Refrigerant Pressure
B7
Compressor Discharge Temperature
B8
Motor Current
Oil Feed Temperature
B9
B10
Leaving Evaporator Water Temperature
Table 6, Compressor Controller, Digital Inputs
#
ID1
Manual Off
ID2
Mech High Pressure
ID3
Motor High Temperature
Vanes Closed Switch
ID4
ID5
Starter Transition
ID6
Starter Fault
Evap Flow
ID7
ID8
Cond Flow
ID9
Vanes Open Switch
8
Description
Primary Evaporator Water Pump
Standby Evaporator Water Pump
Primary Condenser Water Pump
Standby Condenser Water Pump
Tower Fan #1
Tower Fan #2
(unused)
Alarm
Tower Fan #3
Tower Fan #4
Description
Description
Load
Output OFF
Pump Contactor
Pump OFF
Pump Contactor
Pump OFF
Pump Contactor
Pump OFF
Pump Contactor
Pump OFF
Fan Contactor
Fan OFF
Fan Contactor
Fan OFF
Alarm Indicator
Alarm OFF
Fan Contactor
Fan OFF
Fan Contactor
Fan OFF
Output Signal
0 to 10 VDC
0 to 10 VDC
0 to 10 VDC
Signal Source
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.1 to 0.9 VDC
NTC Thermister (10k@25° C)
NTC Thermister (10k@25° C)
0.5 to 4.5 VDC
NTC Thermister (10k@25° C)
0.5 to 4.5 VDC
NTC Thermister (10k@25° C)
NTC Thermister (10k@25° C)
Signal
0 VAC (Off)
0 VAC (High Pressure )
0 VAC (High Temp)
0 VAC (Not Closed)
0 VAC (No Transition)
0 VAC (Fault)
0 VAC (N0 Flow)
0 VAC (N0 Flow)
0 VAC (Not Open)
Output ON
Pump ON
Pump ON
Pump ON
Pump ON
Fan ON
Fan ON
Alarm ON
Fan ON
Fan ON
Range
0 to 100% Open
0 to 100%
0 to 100% Open
Range
0 to 150 psi
0 to 450 psi
0 to 150 psi
-58 to 212° F
-58 to 212° F
0 to 450 psi
-58 to 212° F
0 to 125% RLA
-58 to 212° F
-58 to 212° F
Signal
24 VAC (Auto)
24 VAC (OK)
24 VAC (OK)
24 VAC (Closed)
24 VAC (Transition)
24 VAC (No Fault)
24 VAC (Flow)
24 VAC (Flow)
24 VAC (Open)
OM Centrif Micro ΙΙ-5