McQuay WSC Operating Manual page 27

Microtech ?? for centrifugal chillers and templifiers
Hide thumbs Also See for WSC:
Table of Contents

Advertisement

TIMERS Setpoint
Figure 15, TIMERS Setpoint Screen
Table 13, TIMER Setpoints
Description
Postlube Timer
Unload Timer
Full Load Timer
Interlock
Prelube Timer
Stop-Start
Start-Start
Evap
Recirculate
OM Centrif Micro ΙΙ-5
No.
Default
Range
8
30 sec
10 to 240 sec
7
30 sec
10 to 240 sec
6
300 sec
0 to 999 sec
5
4
30 sec
10 to 240 sec
3
3 min
3 to 20 min
2
40 min
15 to 60 min
15 sec to 5
1
30 sec
min
Pass-
word
T
Time for postlube before compressor can stop
T
Time compressor will unload before going to postlube
T
Time compressor must load for full open vanes
WMC only
T
Time compressor must prelube before starting
Time from when compressor stops to when it can
M
restart
Time from when compressor starts to when it can start
M
again
Time that evaporator pump must run before
M
compressor start
Comments