NOTES:.
1.
If a fault occurs that has a Y in the "Controlled Stop" column, and P21 (Controlled Fault Stop) is set to
On, and P9 (Stop Mode) is set to dcL, then the starter will perform a voltage decel to stop. Otherwise it
will coast to stop.
2.
If a fault occurs that has a Y in the "Auto Reset" column, and P22 (Auto Fault Reset Time) is set to some
value other than OFF, then the fault will automatically be cleared after the time specified by P22.
3.
Manual reset is accomplished by pressing the reset button on the LED display. See Figure 38. A stack
over temperature fault (number 61) requires pressing the reset button located on the stack first.
OM Centrif Micro ΙΙ-5
96
CPU Error – Illegal Instruction Trap
97
CPU Error – Software Watchdog Fault
98
CPU Error – Spurious Interrupt
99
CPU Error – Program Storage Fault
NOTE: If a fault occurs that has a Y in the "Auto Reset" column, and P14 (Auto Fault Reset Time) is set to
some value other than OFF, then the fault will automatically be cleared after the time specified by P14.
Table 31, Faults/Alarms, Solid State Starter
00
No fault
01
UTS (Up To Speed) Time Limit Expired
02
Motor Thermal Overload Trip
10
Phase Rotation Error, not ABC
12
Low Line Frequency
13
High Line Frequency
15
Input power not three phase
21
Low Line L1-L2 Voltage
22
Low Line L2-L3 Voltage
23
Low Line L3-L1 Voltage
24
High Line L1-L2 Voltage
25
High Line L2-L3 Voltage
26
High Line L3-L1 Voltage
27
Phase Loss
28
No Line Voltage
30
I.O.C. (Instantaneous Overcurrent)
31
Overcurrent
37
Current Imbalance
38
Ground Fault
39
No Current at Run
40
Shorted / Open SCR
41
Current While Stopped, Motor Failed To Stop
47
Stack Protection Fault (SCR at Operating Limit)
48
Bypass Contactor Fault (on STOP input)
50
Control Power Low
51
Current Sensor Offset Error
52
Burden Switch Error
60
Thermistor Trip (on DIN#1, Motor Overheat Input)
61
Stack OT Switch Trip (on DIN#2)
71
Analog Input Trip (Not Used)
82
Modbus Timeout (Communication Fault)
95
CPU Error – Parameter Storage Fault
96
CPU Error – Illegal Instruction Trap
97
CPU Error – Software Watchdog Fault
98
CPU Error – Spurious Interrupt
99
CPU Error – Program Storage Fault
Description
Description
Auto Reset
N
N
N
N
Controlled
Auto
Stop
Reset
-
-
Y
Y
Y
N
N
Y
N
Y
N
Y
N
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
Y
N
Y
N
N
Y
N
Y
Y
Y
N
N
Y
N
N
N
N
N
Y
Y
N
N
Y
-
N
N
N
N
N
N
N
Y
Y
Y
Y
N
N
N
N
N
N
N
N
N
N