Cooling TOWER Fan Settings
Figure 18, Cooling TOWER Fan Setpoint Screen (See page 31 for complete explanation.)
Table 16, Tower Fan Settings
Description
Stage #4 On (Lift)
Stage #3 On (Lift)
Stage #2 On (Lift)
Stage #1 On (Lift)
Stage #4 On (Temp)
Stage #3 On (Temp)
Stage #2 On (Temp)
Stage #1 On (Temp)
Stage Differential (Lift)
Stage Differential
(Temp)
Stage Down Time
Stage Up Time
Tower Stages
Valve/VFD Control
Tower Control
30
No.
Default
Range
15
65 psi
10 to 130 psi
14
55 psi
10 to 130 psi
13
45 psi
10 to 130 psi
12
35 psi
10 to 130 psi
11
85 °F
40 to 120 °F
10
80 °F
40 to 120 °F
9
75 °F
40 to 120 °F
8
70 °F
40 to 120 °F
7
6.0 psi
1.0 to 20.0 psi
6
3.0 °F
1.0 to 10.0 °F
5
5 min
1 to 60 min
4
2 min
1 to 60 min
3
2
1 to 4
None, Valve
Setpoint, Valve
2
None
Stage, VFD
Stage, Valve
SP/VFD Stage
None,
1
None
Temperature,
Lift
Pass-
Comments
word
M
Lift pressure for fan stage #4 on
M
Lift pressure for fan stage #3 on
M
Lift pressure for fan stage #2 on
M
Lift pressure for fan stage #1 on
M
Temperature for fan stage #4 on
M
Temperature for fan stage #3 on
M
Temperature for fan stage #2 on
M
Temperature for fan stage #1 on
M
Fan staging deadband with Setpoint # 1=Lift
M
Fan staging deadband with Setpoint #1=Temp
Time delay between stage up/down event and
M
next stage down
Time delay between stage up/down event and
M
next stage up
M
Number of fan stages used
None: No tower valve or VFD
Valve Setpoint: Valve controls to VALVE SP3(4)
& 5(6)
M
Valve Stage: Valve control setpoint changes to
fan stage setpoint
st
VFD Stage: 1
fan is VFD controlled, no valve
Valve Setpoint/VFD Stage: Both valve and VFD
None: No tower fan control
M
Temperature: Fan and valve controlled by EWT
Lift: Fan and valve controlled by lift pressure
OM Centrif Micro ΙΙ-5