McQuay WSC Operating Manual page 87

Microtech ?? for centrifugal chillers and templifiers
Hide thumbs Also See for WSC:
Table of Contents

Advertisement

If the motor does not rotate within a few seconds after a start command, the initial current should
be increased. If the motor takes off too quickly after a start command, the initial current should be
decreased.
The initial current must be set to a value that is lower than the maximum current parameter setting.
A typical setting for the initial current parameter is from 50% to 175%.
Values
The initial current is adjustable from 50% to 400% in 1% intervals.
Default
The default value for the initial current is 100%.
Max. Curr. (maximum current)
Description
The maximum current parameter is set as a percentage of the motor FLA parameter setting. The
maximum current parameter performs two functions. It sets the current for the end of the ramp
profile and sets the maximum current that is allowed to reach the motor while the motor is being
started.
If the ramp time expires before the motor has reached full speed, the starter will hold the current at
the maximum current level until the stall time expires, the motor reaches full speed, or the
overload trips.
Typically, the maximum current is set to 600% unless the power system or load dictates the setting
of a lower maximum current.
Values
The maximum current is adjustable from 100% to 600% in 1% intervals.
Default
The default value for the maximum current is 600%.
Ramp Time
Description
The ramp time sets the amount of time that it takes for the starter to linearly increase the current
from the initial current level to the maximum current level. A typical ramp time setting is from 15
to 30 seconds.
Settings
The ramp time is adjustable from 0 to 120 seconds in 1 second intervals.
Default
The default value for the ramp time is 15 seconds.
Overload
Description
If there is more than one motor connected, the motor FLA should be set to the sum of the
connected motor full load.
amps.
Values
Class 1 to 40 in steps of 1.
Default
The default value for the overload parameter is 10.