Summary of Contents for McQuay MicroTech III
Page 1
Pathfinder Chiller, Model AWS NOTICE Use this manual to physically install the MicroTech III Communication Module into the chiller unit controller and connect the chiller unit controller to your network. Use the appropriate McQuay Engineering Data (ED), known as the Protocol Information document, to integrate the unit into your network.
Parts List ............................. 14 Installation Kit ..........................14 Figures Figure 1. Modbus Communication Module Attached to MicroTech III Chiller Unit Controller ..5 Figure 2. Modbus Communication Module Major Components ............6 Figure 3. Modbus Communication Module and Knockout ..............7 Figure 4.
This manual contains the information you need to install the Modbus Communication Module on a MicroTech III Chiller Unit Controller, incorporate it into the Modbus network, and maintain it. DANGER Dangers indicate a hazardous situation that will result in death or serious injury if not avoided.
The Modbus Communication Module is a printed circuit board with a plastic enclosure that connects to the left side of the McQuay D-Net™ Module as shown in Figure 1 or directly to the unit controller. The Modbus Communication Module provides access to the unit controller variables and parameters via Modbus.
Red flashing with 2Hz = Software error. Hardware error. In the event that this should occur, cycle power to the unit controller to attempt to clear the problem. Contact the McQuay Controls Customer Support Group at 866-4MCQUAY (866-462-7829) for additional assistance if necessary.
, and Ref. The Modbus Communication Module has two RS-485 ports, but only the top connector (Channel 0) is used (see Figure 2). Board-To-Board Connector The board-to-board connector connects the MicroTech III Chiller Unit Controller to the Modbus Communication Module (see Figures 3, 4, and 5). Figure 3. Modbus Communication Module and Knockout...
Installation The following section describes how to field install a new Modbus Communication Module or replace an existing Modbus Communication Module on the MicroTech III Chiller Unit Controller so that it can be incorporated into the Modbus network. CAUTION Electrostatic discharge hazard. Can cause equipment damage.
Electric shock hazard. Can cause personal injury or equipment damage. This equipment must be properly grounded. Only personnel knowledgeable in the operation of the equipment being controlled must perform connections and service to the MicroTech III Chiller Unit Controller. 1. Remove power from the unit controller.
Refer to the appropriate MicroTech III Chiller Unit Controller Operation Manual for default values and keypad operating instructions. Refer to McQuay Protocol Document ED 15121 for descriptions of the available Modbus variables.
5. Verify the Baud Rate as required by the network and change if necessary. 6. Change “Apply Changes” from No to Yes. Figure 6. MicroTech III Chiller Unit Controller Password Menu and Main Features If a password has Back button...
Page 13
BAS. Change remaining parameters as required for your network. Note: To save changes to these parameters, select “Apply Changes” under Modbus Setup. For additional information on using the keypad/display, refer to the appropriate MicroTech III Chiller Unit Controller Operation Manual. Table 1. Network Configuration Menu...
This document contains the most current product information as of this printing. For the most current product information, please go to www.mcquay.com. All McQuay equipment is sold pursuant to McQuay’s Standard Terms and Conditions of Sale and Limited Product Warranty.