MODES Setpoints
Figure 20, MODES Setpoint Screen
Table 18, MODE Setpoint Settings
Description
No.
Comp # 2 Stage
14
Sequence
Comp # 2 Mode
13
Comp #1 Stage
12
Sequence
Comp #1 Mode
11
Max. Comp. ON
10
BAS Protocol
9
Hot Gas Control
8
Point
Hot Gas Bypass
7
Mode
Cond Pump
6
Evap Pump
5
Available Modes
4
Control Source
3
Unit Mode
2
Unit Enable
1
OM Centrif Micro ΙΙ-5
Default
Range
1
1,2, ... (# of Compressors)
Normal, Efficiency, Pump,
Normal
Standby
1
1,2, ... (# of Compressors)
Normal, Efficiency, Pump,
Normal
Standby
1
1-16
None, Local, Remote,
Modbus
BACnet, LonWorks,
MODBUS,
30%
20 to 70%
Normal
Off, Water LWT, %RLA
Pump #1 Only, Pump #2
Pump
Only, Auto Lead, #1 Primary,
#1 Only
#2 Primary
Pump #1 Only, Pump #2
Pump
Only, Auto Lead, #1 Primary,
#1 Only
#2 Primary
COOL, COOL/ICE, ICE,
COOL
COOL/HEAT, HEAT
LOCAL
LOCAL, BAS, SWITCH
COOL
COOL, ICE, HEAT, TEST
OFF
OFF, ON
Pass-
Comments
word
Sets sequence number for # 2 compressor, if 1 it is
M
always first to start, if 2 is always second (Note 1)
Normal uses standard sequencing
Efficiency starts one compressor on each dual unit
M
Pump starts all compressors on one chiller first
Standby uses this compressor only if another fails.
Sets sequence number for # 1 compressor, if 1 it is
M
always first to start, if 2 is always second (Note 1)
M
Ditto No. 12.
M
Total number of compressors minus standby
Sets BAS Standard Protocol to be used or LOCAL
M
if none.
T
LWT or % RLA below which HGBP solenoid is on
T
Sets mode for hot gas operaton
Pump #1 Only, Pump #2 Only, use only these
pumps
M
AUTO, balance hours between #1 and #2
#1 Primary, #2 Primary, if primary fails, use other
Pump #1 Only, Pump #2 Only, use only these
pumps
M
AUTO, balance hours between #1 and #2
#1 Primary, #2 Primary, if primary fails, use other
T
Sets modes that can be selected in SP 2
O
Sets control source
Selects from MODES in SP4
OFF, everything is off. ON, Evap pump on, comp,
O
cond pump and tower on as required to meet LWT
35