McQuay WSC Operating Manual page 14

Microtech ?? for centrifugal chillers and templifiers
Hide thumbs Also See for WSC:
Table of Contents

Advertisement

Table 9, pLAN address and DIP Switch Settings for Controllers Using pLAN.
Chiller
(1)
Dec.
A
Bin.
Dec.
B
Bin.
Dec.
C
Bin.
Dec.
D
Bin.
NOTES for pLAN multi-chiller communication setup:
1. Up to four single or dual compressors can be interconnected.
2. Operator Interface Touch Screen (OITS) setting is not a DIP switch setting. The OITS address is selected
by selecting the 'service' set screen. Then, with the Technician level password active, select the 'pLAN
Comm' button. Buttons A(7), B(15), C(23), D(31) will appear in the middle of the screen, then select the
letters for the OITS address for the chiller that it is on. Then close the screen. Note that A is the default
setting from the factory.
3. For the pCo2 controller, the pLAN address can be confirmed by viewing the DIP switch positions and
comparing to
Table 9
(see picture below)
4. For the pCo3 controller, there are no DIP switches as shown below.
14
Comp 1
Comp 2
Controller
Controller
1
2
100000
010000
9
10
100100
010100
17
18
100010
010010
25
26
100110
010110
(Bin. rows). Up is 'On', indicated by '1'. Down is 'Off', indicated by '0'.Operation.
Unit
Reserved
Controller
5
6
101000
011000
13
14
101100
011100
21
22
101010
011010
29
30
101110
011110
Operator
Reserved
Interface (2)
7
8
N/A
000100
15
16
N/A
000010
23
24
N/A
000110
31
32
N/A
000001
OM Centrif Micro ΙΙ-5