Item
Station type
Number of output points
Rated load voltage
Max. load current
Isolation method
Max. inrush current
Leakage current at OFF
Max. voltage drop at ON
Output response time
OFFON
ONOFF
Surge suppressor
External power supply for
Voltage
output part
Current
Output type
Withstand voltage
Insulation resistance
Noise immunity
Protection degree
Wiring method for common
Protection function
Overload protection
function
Overheat protection
function
External interface
Communication part
Module power supply part
I/O part
Applicable DIN rail
Applicable wire size
For power supply
For I/O
Applicable solderless
Terminal block for module
terminal
power supply and FG
Terminal block for output
Number of occupied stations
Reference response time
Communication cable
Module power supply
Voltage
Current
Weight
*1 Only one wire can be connected to a terminal of the terminal block for module power supply and FG. Multiple wires cannot be connected
to a terminal. Connecting two or more wires may cause a poor contact.
*2 It is recommended to use the bar solderless terminal for wiring.
NZ2MFB1-32T
Slave station
32 points
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
0.5A/point, 5A/common
Photocoupler isolation
Current is limited by the overload protection function.
0.1mA or less
0.3VDC(TYP.)0.5A, 0.6VDC(MAX.)0.5A
0.5ms or less
1.5ms or less (resistance load)
Zener diode
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
25mA or less (TYP. 24VDC per common) External load current is not included.
Sink type
500VAC for 1 minute between all DC external terminals and the ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP2X
32 points/common (two points) (1-wire, screw terminal block type)
Limited current when detecting overcurrent: 1A or more/point
Activated to each point.
Activated to each point.
RJ45 connector
Terminal block for module power supply and FG (Two-piece spring clamp terminal block (push-in
type))
34-point one-piece terminal block
Tightening torque range for terminal screw (M3  5.2 screw): 0.59 to 0.88Nm
TH35-7.5Fe, TH35-7.5Al (compliant with IEC 60715)
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.8mm  2.0mm
Core: 0.3 to 2.0 (22 to 14 AWG)
Page 59 Applicable solderless terminal
*1
Page 62 Applicable solderless terminal
One station
1ms
An Ethernet cable that meets the 100BASE-TX standard
For details, refer to the following.
 CC-Link IE Field Network Basic Reference Manual
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
85mA or less (24VDC, all points ON)
0.30kg
*2