6.2

Setting Switch

IP address setting switch setting

Set the fourth octet of IP address using the IP address setting switch on the front of I/O module.
The setting of IP address setting switch is enabled when the I/O module is powered on. Thus, set this function when the
module is powered off.
Setting procedure
• Set the hundreds place digit to 200 or 100 of IP address setting switch.
• Set the tens place digit to 80, 40, 20, or 10 of IP address setting switch.
• Set the ones place digit to 8, 4, 2, or 1 of IP address setting switch.
Ex.
To set to 235:
200 0
+
+ 0 +
0
+
20 10
+
Setting range
The setting value must be in the range between 1 and 254.
If the value equal to or more than 255 is set, the following events occur.
• A moderate error occurs and ERR. LED turns on.
• The IP address of I/O module will be 192.168.3.100.
• Do not change the IP address setting switch while the module is powered on. Changing the IP address
setting switch while the module is powered on causes a minor error and flashes the ERR. LED. Returning
the IP address setting switch to the previous setting eliminates the error and turns off the ERR. LED.
• Do not set an IP address with duplicated fourth octet in the access range of CC-Link IE Field Network Basic.
Duplicated fourth octet causes the duplicated IP address due to the automatic setting of the first to third
octet, resulting in failure of data link establishment. ( Page 101 Setting IP Addresses and Subnet
Masks)
+
0
+
4
+
0
+
1
= 235