Appendix 5 Processing Time - Mitsubishi Electric NZ2MFB2-16A User Manual

Cc-link ie field network basic remote i/o module
Hide thumbs Also See for NZ2MFB2-16A:
Table of Contents

Advertisement

Appendix 5
Processing Time
For the processing time of CC-Link IE Field Network Basic, refer to the following.
 CC-Link IE Field Network Basic Reference Manual
Response processing time of slave station
This section shows the response processing time of slave station.
■Input reflection processing time of slave station (input)
*1
The input reflection processing time of the slave station (input) = Input response time
+ Internal processing time (0.2ms)
*1 If the input response time is "0ms", use 0.14ms for calculation.
■Output reflection processing time of slave station (output)
The output reflection processing time of the slave station (output) = Output response time (1.5ms at ON  OFF) + Internal
processing time (0.2ms) = 1.7ms