Mitsubishi Electric NZ2MFB2-16A User Manual page 60

Cc-link ie field network basic remote i/o module
Hide thumbs Also See for NZ2MFB2-16A:
Table of Contents

Advertisement

Do not slide the module from the edge of the DIN rail when mounting it. The module may be damaged.
Removal procedure
Remove the module from the DIN rail by reversing the above procedure.
Applicable DIN rail model (compliant with IEC 60715)
• TH35-7.5Fe
• TH35-7.5Al
Interval between DIN rail mounting screws
Tighten the screws at intervals of 200mm or less.
DIN rail stopper
Use a stopper that is attachable to the DIN rail.
6 INSTALLATION AND WIRING
58
6.4 Installation
7.
Slide the DIN rail stopper up to the left side of the
module.
8.
Hold the DIN rail stopper in the direction opposite to the
arrow on the stopper and tighten the screw with a driver.
9.
Install the DIN rail stopper on the right side of the
module in the same procedure.
Install the stopper upside down for the right side.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents