3.2
Performance Specifications
Input module
NZ2MFB2-16A AC input module
Item
Station type
Number of input points
Rated input voltage/rated frequency
Rated input current
Inrush current
Input voltage distortion ratio
Max. number of simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input impedance
Input response time
Withstand voltage
Insulation resistance
Noise immunity
Protection degree
Wiring method for common
External interface
Applicable DIN rail
Applicable wire size
Applicable solderless
terminal
Number of occupied stations
Reference response time
Communication cable
Module power supply
Weight
*1 Only one wire can be connected to a terminal of the terminal block for module power supply and FG. Multiple wires cannot be connected
to a terminal. Connecting two or more wires may cause a poor contact.
*2 It is recommended to use the bar solderless terminal for wiring.
3 SPECIFICATIONS
16
3.2 Performance Specifications
NZ2MFB2-16A
Slave station
16 points
100 to 120VAC (+10%/-15%), 50/60Hz (3Hz)
8.2mA (100VAC, 60Hz), 6.8mA (100VAC, 50Hz)
200mA maximum within 1ms
Within 5%
100%
80VAC or more/5mA or more (50Hz, 60Hz)
30VAC or less/1.7mA or less (50Hz, 60Hz)
Approx. 15k (60Hz), approx. 18k (50Hz)
OFFON
20ms or less (100VAC 60Hz)
ONOFF
1400VACrms for 1 minute between all AC external terminals and the ground
510VACrms for 1 minute between all DC external terminals and the ground
10M or higher between all AC external terminals and the ground, all DC external terminals and the
ground (500VDC insulation resistance tester)
Noise voltage: 1500Vp-p (AC type), 500Vp-p (DC type), noise width 1s, noise frequency 25 to 60Hz
(noise simulator condition)
IP1X
16 points/common (2-wire, screw terminal block type)
Communication part
RJ45 connector
Module power supply part
Terminal block for module power supply and FG (Two-piece spring clamp terminal block (push-in
type))
I/O part
34-point one-piece terminal block
Tightening torque range for terminal screw (M3 5.2 screw): 0.59 to 0.88Nm
TH35-7.5Fe, TH35-7.5Al (compliant with IEC 60715)
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.8mm 2.0mm
For power supply
For I/O
Core: 0.3 to 2.0 (22 to 14 AWG)
Terminal block for module
Page 59 Applicable solderless terminal
*1
power supply and FG
Page 62 Applicable solderless terminal
Terminal block for input
One station
1ms
An Ethernet cable that meets the 100BASE-TX standard
For details, refer to the following.
CC-Link IE Field Network Basic Reference Manual
Voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current
64mA or less (24VDC, all points ON)
0.31kg
*2