Output Module - Mitsubishi Electric NZ2MFB2-16A User Manual

Cc-link ie field network basic remote i/o module
Hide thumbs Also See for NZ2MFB2-16A:
Table of Contents

Advertisement

Output module

NZ2MFB2-16R contact output module
Item
Station type
Number of output points
Rated switching voltage/current
Minimum switching load
Maximum switching load
Output response time
Life
Maximum switching frequency
Surge suppressor
Fuse
Withstand voltage
Insulation resistance
Noise immunity
Protection degree
Wiring method for common
External interface
Applicable DIN rail
Applicable wire size
Applicable solderless
terminal
Number of occupied stations
Reference response time
Communication cable
Module power supply
Weight
*1 Only one wire can be connected to a terminal of the terminal block for module power supply and FG. Multiple wires cannot be connected
to a terminal. Connecting two or more wires may cause a poor contact.
*2 It is recommended to use the bar solderless terminal for wiring.
3 SPECIFICATIONS
22
3.2 Performance Specifications
NZ2MFB2-16R
Slave station
16 points
24VDC 2A (resistance load)/point, 8A/common
240VAC 2A (COS = 1)/point, 8A/common
5VDC 1mA
264VAC 125VDC
OFFON
10ms or less
ONOFF
12ms or less
Mechanical
20 million times or more
Electrical
Rated switching voltage/current load 100 thousand times or more
Page 46 Relay life (contact switching life)
3600 times/hour
None
None
2300VACrms for 1 minute between all AC external terminals and the ground
510VACrms for 1 minute between all DC external terminals and the ground
10M or higher between all AC external terminals and the ground, all DC external terminals and the
ground (500VDC insulation resistance tester)
Noise voltage: 1500Vp-p (AC type), 500Vp-p (DC type), noise width 1s, noise frequency 25 to 60Hz
(noise simulator condition)
IP1X
16 points/common (2-wire, screw terminal block type)
Communication part
RJ45 connector
Module power supply part
Terminal block for module power supply and FG (Two-piece spring clamp terminal block (push-in
type))
I/O part
34-point one-piece terminal block
Tightening torque range for terminal screw (M3  5.2 screw): 0.59 to 0.88Nm
TH35-7.5Fe, TH35-7.5Al (compliant with IEC 60715)
Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.8mm  2.0mm
For power supply
For I/O
Core: 0.3 to 2.0 (22 to 14 AWG)
Page 59 Applicable solderless terminal
Terminal block for module
*1
power supply and FG
Terminal block for output
Page 62 Applicable solderless terminal
One station
1ms
An Ethernet cable that meets the 100BASE-TX standard
For details, refer to the following.
 CC-Link IE Field Network Basic Reference Manual
Voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current
153mA or less (24VDC, all points ON)
0.35kg