Output Module - Mitsubishi Electric NZ2MFB2-16A User Manual

Cc-link ie field network basic remote i/o module
Hide thumbs Also See for NZ2MFB2-16A:
Table of Contents

Advertisement

Output module

Precautions common to all output modules
■Maximum switching frequency when load is driven
The maximum switching frequency imposes a limit on the use; an ON state or an OFF state must not be changed without an
interval of at least one second.
■Load to be connected
When connecting a counter or timer utilizing a DC/DC converter as a load of the output module, select an output module
whose maximum load current is higher than the inrush current of a load to be connected. If the selection is based on the
average current of a load to be connected, an inrush current flows cyclically from the load while the output module is in an ON
state or in operation, which can cause failure of the module. If it is necessary to select a module on the basis of the average
current of a load to be connected, to alleviate the effect of the inrush current, take any of the following corrective actions:
• Connecting a resistor in series with the load
Resistor
Load
Output
module
• Connecting an inductor in series with the load
Inductor Load
Output
module
6 INSTALLATION AND WIRING
6.1 Before Using the I/O Modules
6
45