CHAPTER 3: INTERFACES
Conversion Summary
Report
CAUTION:
Results Window
NOTE:
CAUTION:
NOTE:
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
At the end of the conversion process, the results are summarized in a conversion report.
The report is found under Device Definition in the offline file window.
Figure 3-25: Conversion Report in Offline Window
For future reference, the user is advised to take a printout of the conversion report
immediately after the conversion. All conversion reports are removed and become
inaccessible if the user removes or modifies the converted file from the 8 Series Setup
Software.
The following figure shows an example conversion summary results window.
Figure 3-26: Results Window
The results window has the following columns:
•
Name: the same tree structure as in the offline window, but with status icons
Settings in the results window are linked to setting screens. This means the user can click in
the results window to navigate to the corresponding 8 Series settings window.
•
Value: the converted value for the 8 Series settings file
•
Original Name: setting name of the input file
•
Original Value: setting value of the input file
All other settings available (not shown in the conversion report) in the 8 Series file are
set to default and must be verified by the user before putting the relay into service.
Status Icons
The status icon shows the conversion results:
Manual configuration required
Successful conversion
Value is not supported
Print Report
If desired, the conversion summary report can be printed using the File/Print
command in the EnerVista taskbar or it can be printed from the "GUI" print button.
Although the report shows successful conversion (green checkbox), the settings must still
be verified before putting the relay in service.
SOFTWARE INTERFACE