FRONT CONTROL PANEL INTERFACE
3–14
Self-test Error
Description of Problem How Often the Test is
1
Message
WiFi Default
SSID and Passphrase is
Settings
the factory default
Link Error Primary
Port 1 or Port 4
3
(depending on order
code) is not connected
Link Error
Port 5 is not connected Every 1 second
Secondary
Traffic Error
Abnormally high
Primary
amount of Broadcast
and Uni-cast traffic on
port 1 or port 4
Traffic Error
Abnormally high
Secondary
amount of Broadcast
and Uni-cast traffic on
port 5
Ambient
The ambient
Temperature >80C
temperature
surrounding the
product has exceeded
80C
Event Rate High
Abnormally high
amounts of events have
been generated so the
relay has stopped
logging to prevent
further issues
IRIG-B Failure
A bad IRIG-B input
signal has been
detected
Version Mismatch
CPU and Comms do not
have the same revision
on firmware
SelfTestFWUpdate The updating of the
firmware failed
Remote CAN IO
The value of the cards
Mismatch
in the slots detected by
the Remote IO does not
match the value
validated by the user
configuration
1. – Failure is logged after the detection of 5 consecutive failures
2. $ – is the slot ID (i.e., F, G, H etc.)
Performed
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Boot-up and Every 1
second
Every 1 second
Every 1 second. A
failure is declared after
60 consecutive failures
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 3: INTERFACES
What to do
Set SSID and Passphrase
Ensure Ethernet cable is
connected, check cable
functionality (i.e. physical
damage or perform
continuity test), and ensure
master or peer device is
functioning. If none of these
apply, contact the factory.
Ensure Ethernet cable is
connected, check cable
functionality (i.e. physical
damage or perform
continuity test), and ensure
master or peer device is
functioning. If none of these
apply, contact the factory.
Contact site IT department to
check network for
malfunctioning devices
Contact site IT department to
check network for
malfunctioning devices
Inspect mounting enclosure
for unexpected heat sources
(i.e loose primary cables) and
remove accordingly
Ensure settings are not set
close to nominal ratings.
Ensure FlexLogic equations
do not have impractical
timing for status events
Ensure IRIG-B cable is
connected, check cable
functionality (i.e. physical
damage or perform
continuity test), ensure IRIG-
B receiver is functioning, and
check input signal level (it
may be less than
specification). If none of
these apply, contact the
factory.
Ensure that both the CPU
and Comms FW was
uploaded during the upgrade
process
Re-try uploading firmware. If
the upload doesn't work a
second time contact factory
Fix the remote CANBUS IO
mismatch.