SOFTWARE INTERFACE
Working with Setpoints & Setpoints Files
FASTPATH:
3–24
3.
Expand the Setpoints > Device > Front Panel list item and double click on Display
Properties or Default Screens to open the settings window as shown:
4.
The settings window opens with a corresponding status indicator on the lower left of
the window.
5.
If the status indicator is red, verify that the serial, USB, or Ethernet cable is properly
connected to the relay, and that the relay has been properly configured for
communications (steps described earlier).
The settings can now be edited, printed, or changed. Other setpoint and command
windows can be displayed and edited in a similar manner. "Actual Values" windows are
also available for display. These windows can be arranged, and resized, if desired.
When a settings file is being uploaded to a device, the DEVICE IN SERVICE state (Setpoints >
Device > Installation) switches to "Not Ready" for the duration of the upload. This ensures
that all new settings are applied before the device is operational. Settings file upload
operations include both 1) Enervista 8 Series Setup software menu option "Write Settings
File to Device" and 2) saving Logic Designer changes online.
Individual setting changes from the device front panel or Enervista 8 Series Setup software
Online Window do not change the DEVICE IN SERVICE state.