ELECTRICAL INSTALLATION

Voltage Inputs

CAUTION:

Restricted Earth Fault Inputs

2–22
The 845 relays have four channels for AC voltage inputs, each with an isolating
transformer. Voltage transformers up to a maximum 5000:1 ratio may be used. The
nominal secondary voltage must be in the 10 to 240 V range. The Bus VT connections most
commonly used, wye and delta (or open delta), are shown in the typical wiring diagram.
The single Auxiliary voltage input is commonly used as the "line voltage". The line VT input
channel, used for the synchrocheck feature, can be connected for phase-neutral voltages
V
, V
, or V
; or for phase-phase voltages V
an
bn
cn
Figure 2-24: Line VT Connections
If Delta VTs are used for three-phase voltages, the zero sequence voltage (V0) and
neutral ground polarizing voltage (–V0) are zero. Also, with the Delta VT connection, the
phase-neutral voltage cannot be measured and is not displayed.
Restricted Earth Fault protection is often applied to transformers having grounded Wye
windings to provide ground fault detection for faults near the transformer neutral. Each
current bank on the relay has 3 phase current inputs and one ground input. Any of the
available inputs on the relay current banks can be selected as a signal input for an RGF
element.
The phase and ground input CT connections to the relay are shown below:
Figure 2-25: Restricted Ground Fault Inputs
, V
, or V
ab
bc
ca
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 2: INSTALLATION
as shown.