GE 845 Instruction Manual page 116

Transformer protection system
Hide thumbs Also See for 845:
Table of Contents

Advertisement

SOFTWARE INTERFACE
3–42
Figure 3-22: Metering Element on configured SLD
Device Status Object
The configurable SLD feature in the 8 Series allows only one device status object per SLD
page. The device status does not have any properties. It is simply shown as "Status: [device
status]". This object shows if the transformer is energized/de-energized.
Static Objects
Static objects are used as simple bitmap images or text/drawing blocks to complete the
single line diagram. There is no control associated with these static objects. The static
objects consist of drawing tools, text object, and power system components.
Front Panel Interaction
8 Series relays use the Select-Before-Operate (SBO) mechanism for local control of
breakers and switches [IEC 61850-7-2]. Initially, the diagram can be browsed through all
available breakers and switches by using the navigation keys. After navigation, selection
must be made for the breaker or switch object by pressing the Enter key. After selecting
the desired switch or breaker, control operations can then be carried out on the selected
switch or breaker. The 8 Series allows local opening, closing, tagging, blocking, and
bypassing. Front panel control is only allowed when the relay is in Local Mode.
Navigation
The Single Line Diagram can be accessed in two ways from the front panel of the relay.
The original location for the SLD pages is under
SLD [X]
. However, a more convenient way to access an SLD page is by setting it as a default
home screen at
Setpoints > Device > Front Panel > Home Screens > Home Screen1
home button more than once rotates through the configured home screens. If the desired
SLD is set to home screen 2 through home screen 10, it can be activated by pressing home
button until it appears on the screen. If no home screen is configured, the default screens
become active. If the default screens are disabled,
shown.
Breaker/Switch Browsing and Selection
While in the SLD screen, only one page is active at any point of time. If SLD1 is active, only
breakers and switches on SLD1 can be operated and controlled. By default, when entering
the SLD menu, the screen displays SLD1. SLD2 through SLD6 can be accessed through the
navigation pushbuttons as shown in the following figure: Active element selection with
flash message.
To browse through the control elements on the SLD page, the navigation keys can be used.
On the rugged front panel, the up and down keys can be pressed for navigation and on the
membrane front panel, up, down, left, and right keys can be pressed. With the rugged front
panel navigation, pressing down sequentially rotates through all the available breakers
Status > Summary > Single Line Diagram >
Status > Summary > Values
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 3: INTERFACES
. Pressing
screen is

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents