Modbus Protocol - GE 845 Instruction Manual

Transformer protection system
Hide thumbs Also See for 845:
Table of Contents

Advertisement

DEVICE

Modbus Protocol

4–32
frames it sends. The receiver LRE uses the sequence number of the RCT and the source
MAC address to detect duplicates. It forwards only the first frame of a pair to its upper
layers.
All Ethernet ports and serial communication ports support the Modbus protocol. The only
exception is if the serial port has been configured for DNP or IEC 60870-5-103 operation
(see descriptions below). This allows the EnerVista 8 Series Setup software (which is a
Modbus master application) to communicate to the 845.
The 845 implements a subset of the Modicon Modbus RTU serial communication standard.
The Modbus protocol is hardware-independent. That is, the physical layer can be any of a
variety of standard hardware configurations. This includes USB, RS485, fiber optics, etc.
Modbus is a single master / multiple slave type of protocol suitable for a multi-drop
configuration.
The 845 is always a Modbus slave with a valid slave address range 1 to 254.
DATA FRAME FORMAT AND DATA RATE
One data frame of an asynchronous transmission to or from an 845 typically consists of 1
start bit, 8 data bits, and 1 stop bit. This produces a 10-bit data frame. This is important for
transmission through modems at high bit rates. Modbus protocol can be implemented at
any standard communication speed. The 845 supports operation at 9600, 19200, 38400,
57600, and 115200 bps baud rate. The USB interface supports ModBus TCP/IP.
FUNCTION CODE SUPPORTED
The following functions are supported by the 845:
FUNCTION CODE 03H - Read Setpoints
FUNCTION CODE 04H - Read Actual Values
FUNCTION CODE 05H - Execute Operation
FUNCTION CODE 06H - Store Single Setpoint
FUNCTION CODE 07H - Read Device Status
FUNCTION CODE 08H - Loopback Test
FUNCTION CODE 10H - Store Multiple Setpoints
FUNCTION CODE 42H - Group Settings Read
FUNCTION CODE 43H - Group Settings Write
When a ModBus master such as the EnerVista 8 Series Setup software communicates to
the 845 over Ethernet, the 845 slave address, TCP port number and the 845 IP address for
the associated port must be configured and are also configured within the Master for this
device. The default ModBus TCP port number is 502.
The following ModBus parameters are configurable:
Path:
Setpoints > Device > Communications > Modbus Protocol
MODBUS SLAVE ADDRESS
Range: 1 to 254 in steps of 1
Default: 254
For the RS485 ports each 845 must have a unique address from 1 to 254. Address 0 is
the broadcast address to which all Modbus slave devices listen. Addresses do not have
to be sequential, but no two devices can have the same address, otherwise conflicts
resulting in errors occur. Generally, each device added to the link uses the next higher
address starting at 1.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS