Rtds - GE 845 Instruction Manual

Transformer protection system
Hide thumbs Also See for 845:
Table of Contents

Advertisement

RTDS

RTDs
NOTE:
RTD Maximums
NOTE:
NOTE:
Analog Inputs
6–20
Path:
Metering > RTDs
The Temperature can be displayed in Celsius or Fahrenheit degrees. The selection is made
in Setpoints > Device > Installation > Temperature Display.
RTD 1(13)
Range: -40 to 250°C (temperatures < -40°C are displayed as "Shorted" and temperatures >
250°C are displayed as "Open RTD")
Path:
Metering > RTD Maximums
The Temperature can be displayed in Celsius or Fahrenheit degrees. The selection is made
in Setpoints > Device > Installation > Temperature Display.
Reset RTD
Date/Time
Range: DD/MM/YY hh/mm/ss
Maximum RTD values can be cleared (reset) by setting the value of Setpoints > Records >
Clear Records > RTD Maximums to "ON". Executing this command loads -40°C as the initial
Maximum RTD value.
RTD 1(13)
Max
Range: -40 to 250°C (temperatures < -40°C are displayed as "Shorted" and temperatures >
250°C are displayed as "Open RTD")
RTD 1(13)
Max
Date/Time
Range: DD/MM/YY hh/mm/ss
Path:
Metering > Analog Inputs
Analog Ip 1 (4)
Range: -500000 to 500000 units in steps of 1
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL