Arc Flash Sensor; Sensor Fiber Handling & Storage; Sensor Installation - GE 845 Instruction Manual

Transformer protection system
Hide thumbs Also See for 845:
Table of Contents

Advertisement

MECHANICAL INSTALLATION

Arc Flash Sensor

CAUTION:
Sensor Fiber Handling
& Storage
CAUTION:

Sensor Installation

FASTPATH:
2–10
The Arc Flash sensor houses the fiber optics and membrane that are used to detect the arc
flash. Two mounting screw holes are provided to affix the sensors to the panel.
If the 8 Series is used in the computation for reducing the Hazard Reduction Category
code, operands for sensor failures must be assigned to an auxiliary output relay which
must be connected into the control logic of the breaker equipment to ensure safe
operations when the output relay is asserted. In the event of this assertion, the Hazard
Reduction Category code cannot be maintained unless backup protection is continuing
to maintain it.
Arc Flash sensor fiber is pressure sensitive and must be handled carefully to avoid
damage. Read the following guidelines fully before proceeding.
Care must be taken when handling the Arc Flash sensor fiber, which can be damaged if
twisted, bent, or clamped tightly during installation.
Do not bend sensor fiber sharply, or with a radius of less than 25 mm (1 inch). Sharp
bends can damage the fiber. Do not pull or tug loops of sensor fiber, as sharp bends
may result.
Do not clamp sensor fiber tightly during installation. Sensor fiber should be held in
place loosely for the best long-term performance. Avoid over-tightening ties which
may deform or break the sensor fiber.
Do not pull or tug sensor fiber with force, as this may cause internal damage or
separate the fiber from the cable connector.
Do not twist the sensor fiber, as twisting can damage the fiber resulting in
substandard performance.
Do not attach sensor fiber directly to the bus.
Avoid surface temperatures above 70 °C or 158 °F to prolong the life of the fiber.
Secure all sensor fibers (loosely but securely) away from any moving parts.
Use the factory-provided dust caps on all Arc Flash sensor fiber and connectors when
not in use, to avoid dust contamination in the transceiver and sensor plugs.
Figure 2-13: AF Sensor - front, side and top view
Review the sensor fiber handling guidelines above.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 2: INSTALLATION

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents