CHAPTER 4: SETPOINTS
FASTPATH:
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
TAGGING
Range: Enabled, Disabled
Default: Enabled
When enabled, tagging control is enabled and the TAG key is displayed on the front
panel interface. When a breaker or a switch is tagged both the local and remote control
of the device is inhibited.
Tagging is applied only from the TAG key and is mostly used for maintenance purposes,
and in general when either the open or close control must be inhibited. The tagging cannot
be bypassed and can only be disabled (untagged) by pressing the TAG key again.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
CONTROL
4–309