FLEXLOGIC
4–344
Path:
Settings > FlexLogic > Non-volatile Latches > Latch 1(16)
NV LATCH 1 FUNCTION
Range: Disabled, Enabled
Default: Disabled
The setpoint enables or disables the Non-volatile Latch function.
NV LATCH 1 TYPE
Range: Reset-Dominant, Set-Dominant
Default: Reset-Dominant
The setting characterizes NV LATCH 1 to be set- or reset-dominant.
NV LATCH 1 SET
Range: Any FlexLogic operand
Default: Off
If asserted, this specified FlexLogic operand 'SET' NV LATCH 1.
LATCH 1 RESET
Range: Any FlexLogic operand
Default: Off
If asserted, this specified FlexLogic operand 'RESET' NV LATCH 1.
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS