00.043
RW
Txt
OL
2400 (3), 4800 (4), 9600 (5),
RFC-A
Defines the serial baud rate of the drive
Changing the parameters does not immediately change the serial communications settings. See
Reset Serial Communications (00.045) for more details.
00.044
RW
Num
OL
RFC-A
Used to define the unique address for the drive for the serial interface. The drive is always a slave
address 0 is used to globally address all slaves, and so this address should not be set in this
parameter.
Changing the parameters does not immediately change the serial communications settings. See
Reset Serial Communications (00.045) for more details.
00.045
RW
Bit
OL
RFC-A
Set to On (1) to update communications set-up.
The display will briefly display On and return to Off on reset.
NOTE
00.046
RW
Num
OL
RFC-A
Defines the upper current threshold for the brake. See Brake Controller Brake Release in Parameter
Reference Guide.
40
Serial Baud Rate
600 (1), 1200 (2),
19200 (6), 38400 (7),
57600 (8), 76800 (9),
115200 (10)
Serial Address
1 to 247
Reset Serial Communications
Off (0) or On (1)
Brake Controller Upper Current Threshold
0 to 200 %
19200 (6)
ND
NC
Off (0)
50 %
Unidrive M400 Control Quick Start Guide
US
US
1
US
US
Issue Number: 3