Commissioning
Digital Input Setup
Current Output
Iout at Alarm
Iout at Flow >103%
Low Flow Cut Off
Empty Pipe Detector
TFE Detector
For PROFIBUS PA version
PA Addr. (BUS)
ID Nr Selector
70
Possible parameter settings Factory setting
No Function, Totalizer
Reset(All), Flowrate to Zero,
System Zero Adjust, Totalizer
Stop(All), Only available for
FEP500 / FEH500 are:
Dual Range, Start/Stop
Batching
4 ... 20 mA, 4 ... 12 ... 20 mA 4 - 20 mA
High Alarm, can be set to
21 ... 23 mA or
Low Alarm, can be set to
3.5 ... 3.6 mA
Off (no signaling, current
output holds 20.5 mA), High
Alarm, Low Alarm
0 ... 10 %
On / Off
On / Off
Possible parameter settings Factory setting
0 ... 126
0x9700, 0x9740, 0x3430
FEX300, FEX500
Flowrate to Zero
High Alarm, 21.8 mA
For details refer to Section
9.2.
Off
1 %
Off
Off
126
0x3430
OI/FEX300/FEX500-EN