ABB FEX300 Operating Instruction page 67

Electromagnetic flowmeter processmaster, hygienicmaster
Hide thumbs Also See for FEX300:
Table of Contents

Advertisement

Pulses per Unit
Next
Pulse Width
Next
Damping
Next
Iout at Alarm
Next
Low Alarm Value
Next
High Alarm Value
Next
OI/FEX300/FEX500-EN
Easy Setup
10.000 / m³
Edit
Easy Setup
30.00 ms
Edit
Easy Setup
30.00 ms
Edit
Easy Setup
High Alarm
Edit
Easy Setup
3.5000 mA
Edit
Easy Setup
21.800 mA
Edit
FEX300, FEX500
25. U se
to call up the edit mode.
26. U se
or
to set the required value.
27. U se
to confirm your setting.
28. U se
to call up the edit mode.
29. U se
or
to set the required pulse width.
30. U se
to confirm your setting.
31. U se
to call up the edit mode.
32. U se
or
to set the required damping.
33. U se
to confirm your setting.
34. U se
to call up the edit mode.
35. U se
or
to select the alarm mode.
36. U se
to confirm your selection.
37. U se
to call up the edit mode.
38. U se
or
to set the required current value for
low alarm.
39. U se
to confirm your selection.
40. U se
to call up the edit mode.
41. U se
or
to set the required current value for
high alarm.
42. U se
to confirm your selection.
Commissioning
67