Flowmax
44i

3.3 Overview of default settings

Function
Pulse value
Digital output Q1
Digital output Q2 *
Digital input I1 *
Current output QA
Creeping suppression

3.4 General Information

Please check the following before powering the flowmeter for the first time:
Check the electrical connections and cable allocations.
Check the installation position of the flowmeter. Is the direction of the
arrow on the housing/name plate and the actual flow direction in the pipe
congruent?
Is the measurement pipe completely filled with fluid?
Check the back pressure in the system.
When everything has been checked, switch on power. After 30 minutes with
power running the measuring device reaches the maximum accuracy.
Flowmax 44i is operational!
M I B
Default settings
1 ml/Pulse
Pulse output as PNP (24V) normal open
Empty pipe output as PNP (24V) normal open
No function assigned
Flow as 4-20mA signal
20mA -> 21 l/min at DN10
36 l/min at DN15
60 l/min at DN20
240 l/min at DN25
0.3 l/min at DN10
0.9 l/min at DN15
3.5 l/min at DN20
5.0 l/min at DN25
3. Commissioning
IMPORTANT!