Flowmax
44i
3.2.7 Digital Outputs Q1 and Q2 (Q2 only available with 8-pin plug)
The digital outputs Q1 and Q2 can be used as a pulse output, for signaling the
empty pipe message for controlling a dosing valve or to limit monitoring.
All outputs become high resistant if voltage falls below 16V. The digital outputs
become high resistant after about 100us for 2s when short circuit or overload.
Then it will retrying to actuate the output.
Setting range:
Default setting Q1:
Default setting Q2:
NPN- or PNP-Logic can be selected.
Setting range:
Default setting Q1:
Default setting Q2:
Empty pipe output
0V normal closed
0V normal open
24V normal closed
24V normal open
Pulse output
0V normal closed
0V normal open
24V normal closed
24V normal open
Upper limit output
0V normal closed
0V normal open
24V normal closed
24V normal open
Lower limit output
0V normal closed
0V normal open
24V normal closed
24V normal open
Dosing output
0V normal closed
0V normal open
24V normal closed
24V normal open
Important!
When using the dosing function the output should not be configured as normal
closed!
If the dosing output is configured as normal closed the valve will stay open
after the dosing batch.
M I B
Off, Pulse Output, Dosing, Negative Flow,
Lower Limit, Upper Limit, Empty Pipe
Pulse Output
Empty Pipe
PNP / NPN, normal closed / normal open
PNP normal open
PNP normal open
Empty pipe
Filled, no flow
High resistance
0V
High resistance
High resistance
24V
High resistance
Empty pipe
Filled, no flow
0V
0V
High resistance
High resistance
High resistance
High resistance
Below lower limit
High resistance
0V
High resistance
24V
Below lower limit
0V
High resistance
24V
High resistance
Startup of device
High resistance
High resistance
High resistance
High resistance
0V
24V
Filled, flow
0V
High resistance
0V
High resistance
24V Pulses
24V Pulses
Between the limits
High resistance
0V
High resistance
24V
Betwenn the limits
High resistance
0V
High resistance
24V
While dosing
High resistance
0V
High resistance
24V
3. Commissioning
Above upper limit
0V
High resistance
24V
High resistance
Above upper limit
High resistance
0V
High resistance
24V
Before/after dosing
0V
High resistance
24V
High resistance
IMPORTANT!