Measuring The Operating Limit Of Set Values - ABB RET670 Commissioning Manual

Transformer protection
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
11.4.2.1
120
Table 21:
Test points for phase-to-phase loops A-B (Ohm/phase)
Test point
Reach
Value
1
X
X1
R
0
2
X
0
R
RLdFwd
R
0.5·RFLdFwPP
3
X
0.85·X1
R
0.85·X1·1/tan(60°)+0.5
RFLdFwdPP
4
X
0.85·X1
R
-0.85·X1·tan (AngNegRes-90°)
5
X
0.5·RFLdFwdPP·tan (ArgLd)
R
0.5·RFLdFwdPP
6
X
-0.5·RLdFwd·tan (ArgDir)
R
0.5·RLdFwd
Table
21
is used together with figure 26.

Measuring the operating limit of set values

Procedure:
1.
Supply the IED with healthy conditions for at least two seconds.
2.
Apply the fault condition and slowly decrease the measured impedance to find the
operate value for of the phase-to-ground loop ECG, test point 1, according to figure
25. Compare the result of the measurement with the expected value according to
table 20.
The corresponding binary signals that inform about the operation of the phase
selection measuring elements are available in the local HMI under
Main menu/Test/Function status/Impedance Protection/PhaseSelection(PDIS,
21)/FDPSPDIS:x.
3.
Repeat steps
1
to
2
to figure
25
and table 20.
to find the operate values for the remaining test points according
1MRK 504 165-UUS -
Comments
When RLdFWd < 0,5·RFLdFwPP
When RLdFwd > 0,5·RFLdFwPP
R=0.491·X1+0.5 RFLdFwdPP
Can be limited by RFLdFwPP
Only when RLdFwd < RFLdFwPP
Transformer protection RET670 2.2 ANSI
Commissioning manual