1MRK 504 165-UUS -
11.10.3.8
Transformer protection RET670 2.2 ANSI
Commissioning manual
=
-
×
vl im vb im
,
,
xline il re rline il im
EQUATION2085-ANSI V1 EN
where:
vb
is the complex value of the busbar voltage
il
is the complex value of the line current (secondary side)
rline
is the value of the line resistance
xline
is the value of the line reactance
For comparison with the set-point value, the modulus of U
equation 111.
2
¦ V
¦ = (vl , re)
+ (vl , im)
L
EQUATION2087-ANSI V2 EN
4.
Inject voltage for V
5.
Inject current equal to rated current I2Base.
6.
Confirm on the local HMI that service values for bus voltage and load current are
equal to injected quantities.
7.
Confirm that the calculated value for load voltage, displayed on the local HMI, is
equal to that derived through hand calculations.
8.
When setting OperationLDC set to Enabled, the voltage regulation algorithm uses
the calculated value for load voltage as the regulating quantity to compare against
VSet and the voltage deadband limits VDeadband and VDeadbandInner.
9.
While injecting rated current I2Base into the IED, inject a quantity for V
slightly higher then VSet + |(Rline+jXLine) · I
voltage V
is higher than VSet, and hence no tap change command should be issued
L
from the IED.
10. Reduce the injected voltage for V
confirm that the calculated value for load voltage is below VSet and a tap change
command is issued from the IED.

Parallel voltage regulation

Master follower voltage regulation
1.
For the transformers connected in the parallel group, confirm that OperationPAR is
set to MF.
2.
For parallel operation, it is also recommended to confirm for parallel group
membership, defined by setting TnRXOP in the local HMI under Main menu/
Testing functionality by secondary injection
-
×
,
,
2
equal to setting VSet.
B
slightly below VSet + |(Rline+jXLine) · I
B
Section 11
are according to
L
|. This will ensure that the regulating
L
(Equation 110)
(Equation 111)
that is
B
| and
L
253