Section 10
Testing IED operation
10.7
96
IEC10000032 V1 EN
Figure 20:
PCM600 report tool display after communication interruption
Testing the protection functionality
Each protection function must be tested individually by secondary injection.
•
Verify operating levels (trip) and timers.
•
Verify alarm and blocking signals.
•
Use the disturbance handling tool in PCM600 to evaluate that the protection function
has received the correct data and responded correctly (signaling and timing).
•
Use the event viewer tool in PCM600 to check that only expected events have
occurred.
1MRK 504 165-UUS -
IEC10000032-1-en.vsd
Transformer protection RET670 2.2 ANSI
Commissioning manual