Completing The Test; Voltage-Restrained Time Overcurrent Protection Vrpvoc(51V); Verifying The Settings - ABB RET670 Commissioning Manual

Transformer protection
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
11.5.14.2
11.5.15
11.5.15.1
208
The service value output NSCURR indicating amplitude of negative sequence current in
primary amperes should be 962A approximative.

Completing the test

Continue to test another functions or end the test by changing the Test mode setting to Off.
Restore connections and settings to their original values, if they were changed for testing
purposes. Make sure that all built-in features for this function, which shall be in operation,
are enabled and with correct settings.

Voltage-restrained time overcurrent protection VRPVOC(51V)

Prepare the IED for verification of settings outlined in Section
verify
settings".

Verifying the settings

Verifying settings by secondary injection
1.
Connect the test set for three-phase current injection and three-phase voltage
injection to the appropriate IED terminals.
2.
Go to Main menu/Settings/IED Settings/Current protection/
VoltageRestOverCurr ( 51V,2(I>/V<))/VRPVOC (51V,2(I>/V<)):1/General
and make sure that the function is enabled, that is, Operation is set to Enabled.
3.
The test of the function may be performed by injecting restrain voltage and
increasing the injected current(s). Note the value at which the PICKUP and STOC
signals are set.
In the following equations, restrain voltage is the magnitude of the
minimum phase-to-phase voltage in secondary volts.
The set trip value in secondary amperes is calculated according to the following
equations:
First part of the characteristic (Restrain voltage ≤ 25% of VBase):
_
Picup Curr
IBase
×
×
100
ANSI13000291 V1 EN
Second part of the characteristic (25% of VBase ≤ Restrain voltage ≤ VHighLimit/
100*VBase), valid when setting parameter VDepMode = Slope:
sec
CT
VDepFact
×
CTprim
100
1MRK 504 165-UUS -
"Preparing the IED to
(Equation 91)
Transformer protection RET670 2.2 ANSI
Commissioning manual