Section 15
Troubleshooting
306
TRM-STAT TermStatus - Internal Events
The list of internal events provides valuable information, which can be used during
commissioning and fault tracing.
The internal events are time tagged with a resolution of 1ms and stored in a list. The list
can store up to 40 events. The list is based on the FIFO principle, when it is full, the oldest
event is overwritten. The list cannot be cleared and its content cannot be erased.
The internal events in this list not only refer to faults in the IED, but also to other activities,
such as change of settings, clearing of disturbance reports, and loss of external time
synchronization.
The information can only be retrieved from the Parameter Setting software package. The
PC can be connected either to the port at the front or at the rear of the IED.
These events are logged as internal events.
Table 38:
Events available for the internal event list in the IED
Event message:
INT--FAIL
Off
INT--FAIL
INT--WARNING
Off
INT--WARNING
IOn--Error
Off
IOn--Error
ADMn-Error
Off
ADMn-Error
MIM1-Error
Off
MIM1-Error
INT--RTC
Off
INT--RTC
INT--TSYNC
Off
INT--TSYNC
INT--SETCHGD
DRPC-CLEARED
The events in the internal event list are time tagged with a resolution of 1ms.
This means that, when using the PC for fault tracing, it provides information on the:
Description
Internal fail status
Internal warning status
In/Out module No. n status
Analog/Digital module No. n
status
mA-input module status
Real Time Clock (RTC) status
External time synchronization
status
Any settings in IED changed
All disturbances in Disturbance
report cleared
1MRK 504 165-UUS -
Generating signal:
INT--FAIL (reset event)
INT--FAIL (set event)
lNT--WARNING (reset event)
lNT--WARNING (set event)
IOn--Error (reset event)
IOn--Error (set event)
ADMn-Error (reset event)
ADMn-Error (set event)
MIM1-Error (reset event)
MIM1-Error (set event)
INT--RTC (reset event)
INT--RTC (set event)
INT--TSYNC (reset event)
INT--TSYNC (set event)
Transformer protection RET670 2.2 ANSI
Commissioning manual