Checking The Residual (Ground Fault) Current Trip Value Pickup_N Set Below Pickup_Ph; Checking The Re-Trip And Back-Up Times; Verifying The Re-Trip Mode - ABB RET670 Commissioning Manual

Transformer protection
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
11.5.8.2
11.5.8.3
11.5.8.4
192
1.
Apply the fault condition, including BFI_3P of CCRBRF (50BF), with a current
below set Pickup_PH.
2.
Repeat the fault condition and increase the current in steps until a trip occurs.
3.
Compare the result with the set Pickup_PH.
4.
Disconnect AC and BFI_3P input signals.
If No CBPos Check or Retrip off is set, only back-up trip can be used to
check set IP>.
Checking the residual (ground fault) current trip value
Pickup_PH
Check the low set Pickup_N current where setting FunctionMode = Current and setting
BuTripMode = 1 out of 4
1.
Apply the fault condition, including BFI_3P of CCRBRF (50BF), with a current just
below set Pickup_N.
2.
Repeat the fault condition and increase the current in steps until trip appears.
3.
Compare the result with the set Pickup_N.
4.
Disconnect AC and BFI_3P input signals.

Checking the re-trip and back-up times

The check of the set times can be made in connection with the check of trip values above.
Choose the applicable function and trip mode, such as FunctionMode = Current and
RetripMode = CB Pos Check .
1.
Apply the fault condition, including initiation of CCRBRF (50BF), well above the
set current value. Measure time from BFI_3P of CCRBRF (50BF).
2.
Check the re-trip t1 and back-up trip times t2 and t3.
In applicable cases, the back-up trip for multi-phase pickupt2MPh and back-up trip
2, t2 and t3 can also be checked. To check t2MPh, a two-phase or three-phase
initiation shall be applied.
3.
Disconnect AC and BFI_3P input signals.

Verifying the re-trip mode

Choose the mode below, which corresponds to the actual case.
In the cases below it is assumed that FunctionMode = Current is selected.
1MRK 504 165-UUS -
Pickup_N set below
Transformer protection RET670 2.2 ANSI
Commissioning manual