ABB RET670 Commissioning Manual page 83

Transformer protection
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK 504 165-UUS -
Establishing connection and verifying the IEEE C37.118/1344 communication
Transformer protection RET670 2.2 ANSI
Commissioning manual
2.1. Set Host IP to the PMU IP address configured for the port in use. Here the
LANAB:1 IPAddress (192.168.1.10) is set.
2.2. Set Port to the IED's TCP port set in the PMU under parameter
C37.118TCPport (4712 is default). Alternatively, in order to make an
IEEE1344 communication, the 1344TCPport parameter setting can be used
(4713 is default).
2.3. Set the Protocol as IEEE C37.118.2-2011.
2.4. Set the Device ID Code in PMU Connection Tester per PMU Data Stream ID
Number (IDCODE). The PMU Data Stream ID Number is a user assigned ID
number (1-65534) for each data stream sent out from the PMU and it is defined
under parameter PMUdataStreamIDCODE. (Main menu/Configuration/
Communication/Station communication/phasor measurement/PMU
Report/PMUREPORT:1)
2.5. Make sure that the Configure Alternate Command Channel is set as Not
Defined. The Configure Alternate Command Channel is used to configure a
TCP channel to control the UDP data communication and transfer the header,
configuration and command frames.
2.6. Continue to the section
communication.
3.
Set the Connection Parameters on PMU Connection Tester for UDP communication
according to the PMU configuration.
IEC140000136 V1 EN
3.1. Set the Local Port to UDP destination port defined in the PMU under the
parameter UDPDestPort1 (Default value: 8910).
3.2. Click the Configure Alternate Command Channel to configure the TCP
channel. A new window will pop up. A TCP channel needs to be configured in
order to control the UDP data communicatiuon and transfer the header,
configuration and command frames.
Verifying the IEEE C37.118/1344 TCP
Section 9
IEC140000136-1-en.vsd
77