Completing The Test; Directional Phase Overcurrent Protection, Four Steps Oc4Ptoc (51_67); Verifying The Settings - ABB RET670 Commissioning Manual

Transformer protection
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
11.5.1.2
11.5.2
11.5.2.1
178
Observe: Do not exceed the maximum permitted overloading of the
current circuits in the IED.
5.
Compare the measured operating current with the set value.
6.
Set the operation mode to 2 out of 3 and inject current into one of the phases and then
check that no TRLn signal appears.

Completing the test

Continue to test another function or end the test by changing the TESTMODE setting to
Disabled. Restore connections and settings to their original values, if they were changed
for testing purposes.
Directional phase overcurrent protection, four steps OC4PTOC
(51_67)
Prepare the IED for verification of settings outlined in Section
verify
settings".
Values of the logical signals for D2PTOC are available on the local HMI under Main
menu/Tests/Function status/Current protection/
PhaseOverCurrent4Step(51_67,4(3I>))/OC4PTOC(51_67;4(3I>)):x, where x =
instance number.
The Signal Monitoring in PCM600 shows the same signals that are available on the local
HMI.

Verifying the settings

The verification of the non-directional phase overcurrent function is done
as instructed below, but without applying any polarizing voltage.
1.
Connect the test set for current injection to the appropriate IED phases.
If there is any configuration logic that is used to enable or block any of the four
available overcurrent steps, make sure that the step under test is enabled (for
example, end fault protection).
If 1 out of 3 currents are chosen for operation: Connect the injection current to phases
A and neutral.
If 2 out of 3 currents are chosen for operation: Connect the injection current into
phase A and out from phase B.
1MRK 504 165-UUS -
"Preparing the IED to
Transformer protection RET670 2.2 ANSI
Commissioning manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents