ABB RET670 Commissioning Manual page 120

Transformer protection
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
114
1
11
X1
10
40% of RLdFwd
80% of RLdFwd
ANSI05000368 V1 EN
Figure 23:
Distance protection characteristic with test points for phase-to-phase
measurements
Table 18:
Test points for phase-to-phase loops L1-L2 (Ohm/Loop)
Test point
Reach
Set value
1
X
X1
R
0
2
X
X1
R
R1
3
X
0.8 x X1
R
0.8 x R1
4
X
0.5 x X1
R
0.5 x R1
5
X
0.85 x RFPP x tan (ArgRLd)
R
0.85 x RFPP
6
X
RLdFw x tan (ArgLd)
R
RLdFw
7
X
0
R
RLdFw
8
X
–0.2143 x RFPP/2
R
0.8 x RFPP/2
Table continues on next page
X
2
80%
3
50%
4
12
120°
a
5
6
R
7
13
9
c
20°
8
0.5 x RFPP
ANSI05000368-1-en.vsd
set
set
set
set
+ RFPP/2
set
set
+ RFPP/2
set
1MRK 504 165-UUS -
(O/phase)
Comments
ArgLd = angle for the maximal load
transfer
Exact: 0.8 x RFPP/2 (ArgDir=20°)
Transformer protection RET670 2.2 ANSI
Commissioning manual