ABB RET670 Commissioning Manual page 132

Transformer protection
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
126
Table 24:
Test points for phase-to-phase loops L1-L2 (Ohm/Loop)
Test point
Reach
Set value
1
X
X1
R
0
2
X
X1
R
R1
3
X
0.8 x X1
R
0.8 x R1
4
X
0.5 x X1
R
0.5 x R1
5
X
0.85 x RFPP x tan (LdAngle)
R
0.85 x RFPP
6
X
RLdFwd x tan (LdAngle)
R
RLdFwd
7
X
RLdFw x tan (LdAngle)
R
0
8
X
–0.2143 x RFPP/2
R
0.8 x RFPP/2
9
X
–0.4 x RLdFwd x tan(ArgDir)
R
0.4 x RLdFwd
10
X
0.5 x X1
R
–0.23 x X1
11
X
0.8 x X1
R
–0.37 x X1
12
X
0.5 x X1
R
0.5 x R1
13
X
0
R
0.5 x RFPP
Table 25:
Test points for phase-to-earth L3-G (Ohm/Loop)
Test point
Reach
Value
1
X
(2 x X1
R
0
2
X
(2 x X1
R
2 x R1
Table continues on next page
set
set
set
set
+ RFPP/2
set
set
+ RFPP/2
set
set
set
set
set
set
set
+X0
)/3
set
set
+ X0
)/3
set
set
+ R0
)/3
set
set
1MRK 504 165-UUS -
Comments
LdAngle = angle for the maximal load
transfer
Exact: 0.8 x RFPP/2 (ArgDir)
Exact –0.5 x R1
x tan(ArgNegRes-90)
set
Exact –0.5 x R1
x tan(ArgNegRes-90)
set
Only used when
OperationLdCmp setting
is 0 (Disabled)
Comments
Transformer protection RET670 2.2 ANSI
Commissioning manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents