ABB RET670 Commissioning Manual page 125

Transformer protection
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

1MRK 504 165-UUS -
Transformer protection RET670 2.2 ANSI
Commissioning manual
Table 20:
Test points for phase-to-ground loop CG (Ohm/loop)
Test point
Reach
Value
1
X
[X1+XN]
R
0
2
X
0
R
RLdFwd
R
RFltFwPG
3
X
0.85·[X1+XN]
R
0.85·[X1+XN]
4
X
R
-0.85·[X1+XN]·
tan (AngNegRes-90°)
5
X
RFltFwdPG·tan (LdAngle)
R
RFltFwdPG
6
X
-0,5·RLdFwd·tan (ArgDir)
R
0,5·RLdFwd
Table
20
is used together with figure 25.
4
85%
X1
50% RLdFwd
0.5·RFltFwdPP
ANSI09000735 V1 EN
Figure 26:
Operating characteristic for phase selection function, forward direction
phase-to-phase faults
Testing functionality by secondary injection
W
(
/
phase
)
X
1
5
ArgNegRes
60°
2
7
6
ArgDir
Section 11
Comments
XN=(X
-X
)/3
0
1
When RLdFWd < RFltFwPG
When RLdFwdPG > RFltFwPG
R≈0.491·(X1+XN)+RFltFwdPG
Can be limited by RFltFwPG
Only when RLdFwd < RFltFwPG
3
LdAngle
W
(
/
phase
)
R
ANSI09000735-1-en.vsd
119