No.
Name
Set/Reset Real Time
o4-17
Clock
Auto-Tuning Mode
T1-01
Selection
T1-02
Motor Rated Power
T1-03
Motor Rated Voltage
T1-04
Motor Rated Current
Motor Base
T1-05
Frequency
T1-06
Number of Motor Poles Sets the number of motor poles as specified
(0706)
T1-07
Motor Base Speed
T1-11
Motor Iron Loss
T1-12
T1 Tuning Start
U1-01
Frequency Reference
U1-02
Output Frequency
U1-03
Output Current
Output Voltage
U1-06
Reference
U1-10
Input Terminal Status
YASKAWA ELECTRIC TOEP C710616 54A YASKAWA AC Drive - Z1000 Quick Start Guide
Description
Sets the current date and time for the Real
Time Clock.
0: — — No Setting
1: Real Time Clock Set
2: Real Time Clock Reset
Note:
Available in drive
software versions PRG:
1013 and later.
2: Stationary Auto-Tuning for Line-to-
Line Resistance
3: Rotational Auto-Tuning for V/f Control
Energy Saving
Note:
The availability of certain
Auto-Tuning methods
depends on the control
mode selected for the
drive.
Sets the motor rated power as specified on
the motor nameplate.
Note:
1. Use the following
formula to convert
horsepower into
kilowatts: 1HP = 0.746
kW.
2. Default setting is
dependent on
parameter o2-04,
Drive Model
Selection.
Sets the motor rated voltage as specified on
the motor nameplate.
Sets the motor rated current as specified on
the motor nameplate.
Sets the rated frequency of the motor as
specified on the motor nameplate.
on the motor nameplate.
Sets the rated speed of the motor as
specified on the motor nameplate.
Sets the iron loss for determining the
Energy Saving coefficient.
The value is set to E2-10 (motor iron loss)
set when the power is cycled. If T1-02 is
changed, a default value appropriate for the
motor capacity that was entered will appear.
The drive starts tuning.
Monitors the frequency reference. Display
units are determined by o1-03.
Displays the output frequency. Display
units are determined by o1-03.
Displays the output current.
Displays the output voltage.
Displays the input terminal status.
U1 - 10=
00000000
1
Digital input 1
(terminal S1 enabled)
1
Digital input 2
(terminal S2 enabled)
1
Digital input 3
(terminal S3 enabled)
1
Digital input 4
(terminal S4 enabled)
1
Digital input 5
(terminal S5 enabled)
1
Digital input 6
(terminal S6 enabled)
1
Digital input 7
(terminal S7 enabled)
No.
Name
Output Terminal Status
U1-11
U1-12
Drive Status
Terminal A1 Input
U1-13
Level
Terminal A2 Input
U1-14
Level
Output Frequency after
U1-16
Soft Starter
U1-18
oPE Fault Parameter
MEMOBUS/Modbus
U1-19
Error Code
Software Number
U1-25
(Flash)
U1-26
Software No. (ROM)
U1-27
Message ID (OPR)
U1-28
Message ID (INV)
U5-01
PI Feedback
U5-02
PI Input
U5-03
PI Output
U5-04
PI Setpoint
i.8 Parameter Table
Description
Displays the output terminal status.
U1 - 11= 00000000
1
Multi-Function
Digital Output
(terminal MD-ME-MF)
1
Multi-Function
Digital Output
(terminal M1-M2)
1
Multi-Function
Digital Output
(terminal M3-M4)
0
Not Used
1
Fault Relay
(terminal MA-MC closed
MA/MB-MC open)
Verifies the drive operation status.
U1 - 12=
00000000
1
During run
1
During zero-speed
1
During REV
1
During fault reset
signal input
1
During speed agree
1
Drive ready
1
During alarm
detection
1
During fault detection
Displays the signal level to analog input
terminal A1.
Displays the signal level to analog input
terminal A2.
Displays output frequency with ramp time
and S-curves. Units determined by o1-03.
Displays the parameter number that caused
the oPEoo or Err (EEPROM write error)
error.
Displays the contents of a MEMOBUS/
Modbus error.
U1 - 19=
00000000
1
CRC Error
1
Data Length Error
0
Not Used
1
Parity Error
1
Overrun Error
1
Framing Error
1
Timed Out
0
Not Used
FLASH ID
ROM ID
OPR ID
INV ID
Displays the PI feedback value.
Displays the amount of PI input (deviation
between PI setpoint and feedback).
Displays PI control output.
Displays the PI setpoint.
77