Model
4A0414
4A0480
4A0590
u
UL Standards Compliance
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing and
evaluation, and determined that their stringent standards for product safety have been met. For a product to receive UL
certification, all components inside that product must also receive UL certification.
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions described
below must be met to maintain compliance when using this drive in combination with other equipment:
n
Installation Area
Do not install the drive to an area greater than pollution degree 2 (UL standard).
n
Ambient Temperature
IP20/NEMA 1, UL Type 1 Enclosure, External Heatsink (2A0011 to 2A0073 and 4A0005 to 4A0302): -10 to +40 °C (14 to
104 °F)
IP00/Open Type Enclosure (2A0343 and 2A0396 and 4A0361 to 4A0590): -10 to +50 °C (14 to 122 °F)
n
Main Circuit Terminal Wiring
Yaskawa recommends using closed-loop crimp terminals on all drive models. To maintain UL/cUL approval, UL Listed
closed-loop crimp terminals are specifically required when wiring the drive main circuit terminals on models 2A0031 to
2A0396 and 4A0034 to 4A0590. Use only the tools recommended by the terminal manufacturer for crimping.
Loop Crimp Terminal Size on page 84
YASKAWA ELECTRIC TOEP C710616 54A YASKAWA AC Drive - Z1000 Quick Start Guide
Type
Rated Current (A)
FS5972-600-99
FS5972-800-99
W
Y
Figure i.64 EMC Filter Dimensions
Figure i.65 UL/cUL Mark
for closed-loop crimp terminal recommendations.
Filter Data (Manufacturer: Schaffner)
Weight (lb)
600
24.3
800
69.4
D
i.9 Standards Compliance
Dimensions
Y x X (in)
[W x D x H] (in)
10.2 × 5.3 × 15.2
9.3 × 4.7
11.8 × 6.3 × 28.2
10.8 × 8.3
Refer to Closed-
83