YASKAWA Z1000 Quick Start Manual page 84

Ac drive for hvac fan and pump
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

i.9 Standards Compliance
The wire gauges listed in the following tables are Yaskawa recommendations. Refer to NEC table 310-16 for proper wire
gauge selection for terminals -M, +M, -1, +3, and ground.
Wire Gauges and Tightening Torques
Refer to Wire Gauges and Tightening Torque on page 23
United States.
Closed-Loop Crimp Terminal Recommendations
Yaskawa recommends using closed-loop crimp terminals on all drive models. To maintain UL/cUL approval, UL Listed
closed-loop crimp terminals are specifically required when wiring the drive main circuit terminals on models 2A0031 to
2A0396 and 4A0034 to 4A0590. Use only the tools recommended by the terminal manufacturer for crimping. Yaskawa
recommends crimp terminals made by JST and Tokyo DIP (or equivalent) for the insulation cap.
Table i.34
matches the wire gauges and terminal screw sizes with Yaskawa-recommended crimp terminals, tools, and insulation
caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge and screw size for your drive
model. Place orders with a Yaskawa representative or the Yaskawa sales department. Refer to local codes for proper selections.
Terminal
Wire Gauge
Screws
2
2 mm
M4
14 AWG
2
3.5 / 5.5 mm
M4
12 / 10 AWG
M4
2
8 mm
8 AWG
M5
M5
2
14 mm
6 AWG
M8
M5
2
22 mm
4 AWG
M8
2
30 / 38 mm
M8
3 / 2 AWG
2
50 / 60 mm
1 AWG
M8
1/0 AWG
1/0 AWG × 2P
2
70 mm
M8
2/0 AWG
2/0 AWG × 2P
M10
M10
2
80 mm
3/0 AWG × 2P
M12
3/0 AWG × 4P
2
100 mm
M12
4/0 AWG × 2P
4/0 AWG × 4P
2
150 mm
M12
250 kcmil × 2P
300 kcmil × 2P
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user should
order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user
should order four sets of [100-051-560].
Note:
Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.
84
to select the appropriate wires and crimp terminals for use in the
Table i.34 Closed-Loop Crimp Terminal Size
Crimp Terminal
Model Number
Machine No.
R2-4
YA-4
5.5-4NS
YA-4
8-4NS
YA-4
R8-5
YA-4
R14-5
YA-4
R14-8
YA-5
22-5NS
YA-5
R22-8
YA-5
R38-8
YA-5
R60-8
YA-5
CB70-S8
YF-1 YET-300-1
70-8
70-10
YF-1 YET-300-1
80-10
YF-1 YET-300-1
80-L12
YF-1 YET-300-1
100-L12
YF-1 YET-300-1
150-L12
YF-1 YET-300-1
YASKAWA ELECTRIC TOEP C710616 54A YASKAWA AC Drive - Z1000 Quick Start Guide
Tool
Die Jaw
AD-900
AD-900
AD-901
AD-901
AD-902
AD-952
AD-953
AD-953
AD-954
AD-955
TD-322,TD-311
TD-322,TD-311
TD-323,TD-312
TD-323,TD-312
TD-324,TD-312
TD-325,TD-313
Insulation
<1>
Cap
Code
Model No.
TP-003
100-054-028
TP-005
100-064-248
TP-008
100-064-249
TP-008
100-054-032
TP-014
100-054-034
TP-014
100-054-035
TP-022
100-051-262
TP-022
100-051-263
TP-038
100-051-264
TP-060
100-051-265
100-064-417
TP-080
100-064-250
TP-080
100-064-251
TP-080
100-051-267
TP-080
100-051-558
TP-100
100-051-560
TP-150
100-051-562

Hide quick links: